Menai Meats were continually failing their COD and S/S consents (with the threat of closure) as they had no facilities on site to biologically reduce the strength of their effluent. To screen out the gross solids from the effluent they have had Groundhog Separators installed since 1995. Pollution Control supplied a re-conditioned (ex-hire) high performance modular Eco-SAF biological system
Menai Meats were continually failing their COD and S/S consents (with the threat of closure) as they had no facilities on site to biologically reduce the strength of their effluent. To screen out the gross solids from the effluent they have had Groundhog Separators installed since 1995. Pollution Control supplied a re-conditioned (ex-hire) high performance modular Eco-SAF biological system comprising of:
Flow | 110m3/day |
Maximum COD | 5270mg/l |
Maximum S/S | 840mg/l |
Max hydraulic loading | 12m3/hour |
Design flow | 0.8l/s |
The on-site effluent treatment system is to treat the site wastewater to the minimum trade effluent quality as follows:
Parameter | Unit | Permitted Discharge | Achieved discharge |
---|---|---|---|
COD (settled) | mg/l | 3000 | 800-900 |
BOD (5 day settled) | mg/l | 1200 | 300-360 |
Suspended solids | mg/l | 120 | 200-250 |
Comprising of the following elements:
The Eco-SAF module – the essential biological stage where bacterial microorganisms are cultivated and actively consume the suspended organic material found in the decanted liquid from the primary process. The aerated cells are equipped with a fine-bubble aeration system distributing the oxygen required by the heterotrophic bacteria to grow. Oxygen is supplied to the air diffuser system by side channel blower that requires minimum maintenance.
The module is a series of aerated cells and anoxic zones. The aerated cells are also furnished with fully submerged bio-film growth media to ensure that the microorganisms have a substantial area for growth and a stable environment. Full floor coverage with the aeration diffusers ensures there is maximum oxygen transfer and there are no ‘unaerated’ dead zones as in circular tank designs.